BraVeBo B.V. – Certified Fire & Smoke Seals & Premium Interior Finishing

Specialist in Certified Passive Fire Protection: Total Risk Mitigation

In case of fire, there is no second chance!

Firestop seals explained WBDBO 🔥 & WRD 💨

WBDBO (EI/EIW) + WRD (Ra/R200, Sa/S200): the Dutch framework for fire and smoke resistant compartmentation in accordance with Bbl, NEN 6068 and NEN 6075.

This page is a technical explainer for design, construction and FM teams. Here you will find:

🔥 Fire seals in practice – our service

💨 WRD in practice – smoke-resistant seals

WRD – Smoke resistance in plain language

Fire is not the only problem – smoke is

Most people know fire resistance in minutes:

That indicates how long a wall, floor, door or penetration will resist fire and high temperature.

In real fires, smoke is often more dangerous than flames:

That is why, in the Netherlands, we do not stop at EI alone.

The Bbl (Besluit bouwwerken leefomgeving – Building Decree) also uses WRD:

WRD = Weerstand tegen RookDoorgang (resistance to smoke passage) → how well a separation stops smoke.

Fire safety in NL = EI + WRD Not EI alone.

What is WRD?

WRD indicates how well a wall, floor, ceiling or door set prevents smoke from leaking from one space to another.

NEN 6075 uses two levels:

For individual components (such as a door, hatch or damper), European standards use:

You can think of it like this:

The separation only works properly if all components together keep the smoke where it belongs.

Where is WRD especially important?

WRD is especially important where people must be able to escape safely:

In these locations, Dutch law says:

The separation must be smoke resistant, and WRD must be determined according to NEN 6075.

In these zones the rule is very simple: EI alone is not enough. You need EI and WRD.

Why “EI only” is not enough

A wall or door can be EI 60 and still allow a lot of smoke through:

In short:

For safe escape routes in Dutch buildings – especially in stairwells and escape corridors – you need both:

EI + WRD – not EI alone.

An EI certificate without WRD therefore does not cover the full legal requirement where the Bbl prescribes a smoke-resistant separation.

When is WRD (NEN 6075) mandatory in NL?

Core principles

Very briefly, it works like this:

The usual European fire tests:

are about fire resistance (E / EI / EW) – not about WRD. They are input for EI / WBDBO, not for Ra / R200.

So:

Where both apply, both must be satisfied.

Everywhere the Bbl requires a smoke-resistant separation, WRD according to NEN 6075 is a legal requirement, not an optional extra.

New-build – sub-fire compartments (SBC)

For new-build, the Bbl requires that a sub-fire compartment (SBC):

WRD is then mandatory for separations:

Key concept:

As soon as a separation both:

WRD according to NEN 6075 formally becomes mandatory.

Existing buildings

In existing buildings the WRD requirement does not disappear. The Bbl sets a minimum level, for example:

Technically, this often comes down to at least a separation that behaves as Ra, and in more critical situations effectively as R200.

In renovation or refurbishment projects – for example where a dwelling opens onto a corridor with a protected escape route – the required WRD may again move towards R200.

Rule of thumb:

If a separation has a smoke separation function for escape, WRD according to NEN 6075 is mandatory – often Ra / “20 minutes”, and in more demanding situations R200.

Stairwells and escape routes

A stairwell is usually part of the escape route and is often:

Consequences:

The separations between spaces / SBCs and the stairwell must then comply with both:

So:

If a stairwell is a protected escape route, all connecting walls and doors must comply with WRD – not just EI.

A simple “EI 60 door” is, in that context, legally and technically insufficient.

BC ↔ BC and WRD

Between fire compartments (BC ↔ BC) the main requirement is WBDBO, checked via NEN 6068.

WRD according to NEN 6075 only becomes mandatory if that same separation also:

Examples:

ISSO-SBR 809 in practice

ISSO publication 809 – Fire-safe penetrations:

In one sentence:

Why EI-only is legally insufficient where WRD is required

What EI does and does not cover

EI from EN tests (EN 1366 / EN 1634-1 / EN 1364 / EN 1365) describes fire resistance:

These tests result in E / EI / EW classifications (via EN 13501-2).

They do not provide:

EI does not measure:

By contrast, WRD according to NEN 6075:

Result:

A wall, door or penetration can be perfectly EI 60 and still behave like a smoke sieve.

In that case it fails WRD – and does not comply with the Bbl requirement for a smoke separation.

Components vs separation: Sa / S200 vs Ra / R200

NEN 6075 makes a clear distinction:

To comply with the legal WRD requirement, you must:

EI-only test reports say nothing about this and do not prove WRD.

The essence in short

Putting it all together:

Therefore:

In every Dutch situation where the Bbl requires a smoke-resistant separation, a solution with EI alone is objectively and legally inadequate.

You must also demonstrate WRD according to NEN 6075, usually by:

R vs S – the notation at a glance

To keep it clear:

What each standard does and does not give you (short)

Standard / documentScope (short)Fire resistance (E / EI / EW / R)?Smoke class (Sa / S200)?WRD (Ra / R200)?Explanation
EN 1366-1Ventilation ductsYesNoNoFire resistance of ducts. Input for EI / WBDBO, not for WRD.
EN 1366-2Fire dampersYesNo (unless smoke-tested)NoFire only. Smoke requires separate Sa/S200 substantiation.
EN 1366-3Penetration sealsYesNoNoFire-resistant penetrations. No WRD class.
EN 1366-5Service shafts and ductsYesNoNoMulti-service shafts. Fire only.
EN 1366-8 / -9Smoke extract systemsYes (fire + function)Sometimes smoke criteriaNoFocused on smoke extraction, not room-to-room WRD.
EN 1364-1 / -2Non-loadbearing walls/ceilingsYesNoNoFire resistance of separating constructions.
EN 1365 (series)Loadbearing walls/floors/roofsYes (R / RE / REI)NoNoStructural fire resistance.
EN 1634-1Fire resistance of doors/shuttersYesNoNoFire classification only.
EN 1634-3Smoke control doors/assembliesNo (fire)Yes (Sa / S200)NoProvides Sa/S200 input for NEN 6075.
EN 13501-2Fire classification of elementsE / EI / EW / RNoNoConverts test results into fire classes.
NEN 6068WBDBO – fire spread between spacesUses EI/EW as inputNoNoDetermines fire spread between compartments.
NEN 6075WRD – smoke spread between spacesNoUses Sa/S200 as inputYes (Ra / R200)Determines WRD of the separation as a whole.
ISSO-SBR 809Practical guide for penetrationsDepends on systemDepends on systemHelps to achieveFocused on execution to maintain EI & WRD.

Legend (short):

Do you want to know whether your design or building complies with Dutch WRD requirements? Contact BraVeBo B.V. for an EI + WRD compliance check.

🔒 Request EI 🔥 + WRD 💨 compliance check

Demonstrable compliance: the core standards

Compliance areaStandard / certificationTechnical description & assurance
Fire resistanceNEN 6068 (Bbl) (WBDBO) Resistance to fire spread between compartmentsLimits fire spread and flashover between compartments for the required time; safeguards compartment boundaries.
Smoke resistanceNEN 6075 — Sa and S200 (WRD) Resistance to smoke passageLimits smoke passage; protects escape routes and sensitive electronics against toxic smoke.
PenetrationsNEN-EN 1366-3 (test method)European test method for fire resistance of penetrations; validates system integrity under extreme load.
Linear jointsNEN-EN 1366-4 (test method)Required test method for linear joints in walls and floors; safeguards compartmentation integrity.
Safety managementVCA VOL certificateDemonstrates company-wide competence in safety, health and environment for high-risk activities.

In the Netherlands and the EU, effective fire sealing is a legal requirement under the Besluit bouwwerken leefomgeving (Bbl). Under CPR (EU 305/2011), products that fall under a harmonised standard or are assessed via ETA (EAD/ETAG 026 route) must be provided with a Declaration of Performance (DoP) and CE marking.

In addition, building owners and users/managers have an ongoing legal responsibility to maintain all fire safety provisions. This includes continuously safeguarding the integrity of certified fire seals and fire compartments – a mandatory condition for the operating permit.

Traceability: your audited proof of safety

We provide documented, audited proof of safety. Our focus on traceability creates trust and limits liability.

What we guarantee:

Your benefit: faster inspections, audits and insurance claims, direct traceability for re-entry, and a stronger legal position.

Certified BraVeBo firestop label with QR for traceability alt
Traceable firestop seal

Standards & regulations – overview

EN 1366 — fire resistance tests (series)

EN 1634 — doors & shutters

Classification & Dutch frameworks

Smoke and heat control systems

Practical guidelines & competencies

Frequently asked questions (WBDBO/WRD)

What is WBDBO?

WBDBO stands for Weerstand tegen BrandDoorslag en BrandOverslag – the resistance of a construction against fire spread and flashover between compartments. In the Netherlands this is assessed according to NEN 6068.

What is WRD (Sa / S200)?

WRD means Weerstand tegen RookDoorgang – the resistance of a construction against smoke passage, according to NEN 6075.

These classes are used for components (e.g. doors tested according to EN 1634-3) and form input for the Ra/R200 assessment.

Which tests apply to penetrations and joints?

Classification is done according to EN 13501-2.

Do you provide audit-ready documentation with QR traceability?

Yes. Every seal receives a unique QR code and label. We record photo logs, position, material batch and provide a complete dossier ready for audits, inspections and insurance queries.

Which penetrations and openings do you treat?

Cable bundles, metallic and plastic pipes, ventilation/smoke ducts, linear joints and irregular openings. We select the tested system based on geometry, required classification, movement and environment.

How does BraVeBo ensure compliance in high-security environments?

We use authorised systems (such as Firetect), work in accordance with the relevant EN 1366 series and ISSO-SBR 809, and follow site-specific procedures. Planning, access and handover are aligned with the critical processes of the site.

Do you want to know whether your design or building complies with Dutch EI + WRD requirements?

🔒 Request EI 🔥 + WRD 💨 compliance check

Contact

Naam: Ernestas Belaūsas — Algemeen Directeur

Locatie: Zoetermeer, Zuid-Holland

Werkgebied: Nederland Nederland